ADS-SHR-DOC-SPECTECH
  • UiTM/W1/PER/SHR/B/0425/0002
  • CADANGAN MEMBUKA, MEMBEKAL, MEMASANG DAN MENGUJILARI PERALATAN RANGKAIAN DI MAKMAL AUTOCAD BLOK C UITM CAWANGAN SARAWAK KAMPUS SAMARAHAN
  • Unshielded Twisted Pair (UTP) Cabling Node End-to-End
  • 1. NODE END-TO-END
  • 32 Unit

Maklumat Spesifikasi Teknikal

  
Keterangan Calit Tawaran/Catatan
1. PROJECTS REQUIREMENT -
I. Tenderer needs to install cat 6 UTP cable and dismantle existing UTP cabling. It is up to the tenderer whether to install new cabling or dismantle the old cable. Can be done according to tenderers convenience. Notes: Please refer to UiTM Staff for detailed work location.
Ya

Tidak
II. Tenderer should make additions of the nodes if there is any insufficient without any charges to UiTM.
Ya

Tidak
III. Tenderer MUST ensure all UTP cabling installation to be done by certified personnel.

**PLEASE ATTACH CV. PLEASE MAKE SURE NO TO DISCLOSE ANY INFORMATION RELATED TO THE COMPANY'S NAME, LOGO, REGISTRATION NUMBER, ETC. THIS INFORMATION MUST BE ERASED AND NOT BE READABLE.
Ya

Tidak
IV. Tenderer shall submit installation report for each nodes to UiTM for approval.
Ya

Tidak
V. Tenderer should ensure all existing network equipment/component/cabling is functioning before and after project implementation. Tenderer MUST responsible for any issue as listed above.
Ya

Tidak
2. PRODUCTS REQUIREMENTS -
I. The intra-building UTP CAT 6 cabling is required to provide network nodes end-to-end solution from faceplate to patch panel.
Ya

Tidak
II. The UTP-based cabling system shall have a 250 MHz Channel Bandwidth over a maximum distance of 100 meter (328 ft) and a positive channel Attenuation-to- Power Sum Crosstalk Ratio (PSACR) at 250 MHz.
Ya

Tidak
III. The UTP-based cabling system shall use matched components from a single manufacturer, and the cabling system shall certified to deliver system performance over the lifetime of the applications for which the cabling system was originally designed to support.Please attach the Authorized Letter (LOA) from principle.
Ya

Tidak
IV. All components used in the UTP-based cabling system shall have warranty for a period of at least 20 years from date of installation against defects in materials and/or workmanship. Please attach the letter of warranty (LOW) from principle.
Ya

Tidak
V. The UTP cabling shall include all necessary items for a complete installation such as a proper trunking and conduit, patch cords, cross-connect cables, cable guides, RJ45 modular jack and other accessories required to connect specified end-stations (faceplate) to the patch panel.
Ya

Tidak
VI. All horizontal cabling shall be at least of Category 6 UTP cable or above and must comply with EIA/TIA recommended standard.
Ya

Tidak
VII. Adequate numbers of UTP patch panels shall be provided and must equip with modular jack for the UTP cables termination in the proposed rack.
Ya

Tidak
VIII. All proposed UTP cables must be terminated into RJ-45 outlets contained in faceplates and UTP patch panel. Each faceplate may consist of one or more RJ45 outlets depending on UiTM requirement.
Ya

Tidak
IX. Tenderer must follow the standard specification electrical material approve list by JKR. Please attach material approve list by JKR.
Ya

Tidak
X. Tenderer MUST proposed and provide genuine product. Please attach Authorized Letter (LOA) from principle.
Ya

Tidak
XI. The product MUST be a new product and had been in the market for less than 18 months.
Ya

Tidak
3. CABLE LABELING -
I. Tenderer shall ensure all cable-ends must be labeled and the label must be easily read, lasting and waterproof.
Ya

Tidak
II. Tenderer shall provide the test result for each network point by hardcopy.
Ya

Tidak
4. TECHNICAL/OPERATING MANUAL, ENGINEERING SERVICES AND OTHER ACCESSORIES -
I. Tenderer shall provide user operating/technical manual for UiTM referral.
Ya

Tidak
II. All necessary adapters, cables and other accessories required shall be provided in order to allow the system to work
Ya

Tidak
5. WARRANTY -
I. Twenty (20) years of maintenance support from principle consists of equipment part replacement WHICH covers all permanent copper cabling, outlets and jacks within the horizontal cabling structured cabling system which has been tested and certified. **Please attach Letter of Warranty (LoW) from Principle.
Ya

Tidak
6. DELIVERY PERIOD -
I. Delivery period must be within 18 weeks after tenderer has received the Offer Letter.
Ya

Tidak
II. If there is a delay in project delivery, Tenderer must apply for extension at least 1 month before the delivery period ends.
Ya

Tidak
7. CATALOGUE / BROCHURES Ya

Tidak
I. Tenderer shall provide all related catalogue/brochures
Ya

Tidak