ADS-TDR-DOC-SPECTECH
  • UiTM/B4/PER/T/B/0625/0001
  • MENAIK TARAF SISTEM RANGKAIAN TANPA WAYAR (WIFI) DI KOLEJ KEDIAMAN PELAJAR BAGI UiTM CAWANGAN SELANGOR KAMPUS SUNGAI BULOH, SELANGOR
  • Uninterruptible Power Supply (UPS)
  • UPS 10KVA-(F2_KSB)_RP4
  • 1 Unit

Maklumat Spesifikasi Teknikal

  
Keterangan Calit Tawaran/Catatan
1. General Requirements -
I.
Vendors Is Allowed To Propose Specification Which Is Superior Than The Requirements Specified In This Document, If Required
-
II. The proposed equipment must have a local services center to provide a full technical support and maintenance
Ya

Tidak
III. All related catalogues/brochures shall be provided by the vendor
Ya

Tidak
IV. **PLEASE DO NOT DISCLOSE ANY INFORMATION RELATED TO THE COMPANY'S NAME, LOGO, REGISTRATION NUMBER, ETC. THIS INFORMATION MUST BE ERASED AND NOT BE READABLE
Noted : Please refer to UiTM staff for detailed installation location
Ya

Tidak
2. TECHNICAL SPECIFICATION Ya

Tidak
I. The proposed equipment must provide comprehensive protection against surges and spikes
Ya

Tidak
II. Must provide clean and stable power to connected equipment while its embedded microprocessor controller guarantees high reliability
Ya

Tidak
III. Must provide Green Power Function to achieve lower power consumption for energy saving
Ya

Tidak
IV. ELECTRICAL OUTPUT
Ya

Tidak
A ) Voltage : 208/220/230/240VAC
Ya

Tidak
B ) Frequency: 46- 54Hz or 56- 64Hz
Ya

Tidak
C ) Phase : Single Phase
Ya

Tidak
D ) Efficiency: 91% - 93% depending on load
Ya

Tidak
E ) Voltage Distortion :less than 5% of THD at rate non-linear load : less than 3% of THD at rate linear load
Ya

Tidak
V. POWER
-
A ) Rating: at least 10KVA at pf 0.9
Ya

Tidak
B ) Rating: Double-Conversion Online UPS.
Ya

Tidak
VI. ELECTRICAL INPUT
-
A ) Nominal Voltage : 208/220/230/240VAC
Ya

Tidak
B ) Voltage Range: 110-300VAC at 50% Load, 176-300VAC at 100% Load
Ya

Tidak
C ) Rated Frequency : 40Hz – 70Hz
Ya

Tidak
D ) Power Factor: greater than 99% at Nominal Voltage (100% Load)
Ya

Tidak
E ) Efficiency = 93% at AC Mode, 91% at Battery Mode.
Ya

Tidak
VII. BATTERY
-
A ) Type: Sealed, Maintenance-free lead-acid battery
Ya

Tidak
B ) Number of batteries: 9 Ah, 12 V, 16 pcs.
Ya

Tidak
C ) Back-up time: 3 minutes at full load
Ya

Tidak
D ) Recharge time: 4 hrs to 90% capacity
Ya

Tidak
VIII. CONTROL FEATURES

-
A ) User Interface: Monitoring panel with LCD/LED display : UPS on, Line on, Battery operation, Bypass, Audible alarm
Ya

Tidak
B )
  1. Serial Communications Port: RS232

Ya

Tidak
IX. ENVIRONMENTAL
Ya

Tidak
A )
  1. Ambient Temperature:
    • 0 degree celsius to 40 degree celsius operating
Ya

Tidak
B ) Humidity: 0 to 95% RH non-condensing
Ya

Tidak
C ) Audible Noise: 58 dBA (1M from surface)
Ya

Tidak
X. PHYSICAL
Ya

Tidak
A ) Dimension : 580mm x 438mm x 133 (3u). + 580mm x 438mm x 133mm (3u)
Ya

Tidak
B ) At least weight : 69kg
Ya

Tidak
C ) Type : 2-in-1 Rackmount-Tower (Display can be rotate)

Ya

Tidak
XI. COMMUNICATIONS
-
A ) SNMP Web-Pro for Manage and Monitor UPS.

Ya

Tidak
3. TECHNICAL/OPERATING MANUAL, ENGINEERING SERVICES & OTHER ACCESSORIES

-
I. User manual/operating manual must be provided by the vendor
Ya

Tidak
II. All other related material, components and cabling which are not specified but required to ensure full operation must be supplied by the vendor
Ya

Tidak
4. SUPPORT & WARRANTY
-
I. Delivery cost of the equipment is borne by the vendor
Ya

Tidak
II. Must provide comprehensive and extensive after sales service on labor and overall parts

Ya

Tidak
III. All other related software, material, components and cabling which are not specified but are required to ensure full integration of the item MUST be provided.
Ya

Tidak
5. INSTALLATION & TRAINING: -
I. Pre requisite of requirement of installation, testing and commissioning on site for the supplied package and components MUST be done by tenderer
Ya

Tidak
II. Tendered MUST provide Transfer Technology Session (TOT) training for configuration, operation and maintenance of the system which must cover Rack Mountable Base Unit System Intelligent and UPS Management Software for UiTM's personnel.(Plase specify details of the training by providing
syllabus/guideline).
Ya

Tidak
III. Minimum of three (3) participants on Server and System Management training session
Ya

Tidak
IV. Original training materials (hard copy and soft copy) and documentation MUST be provided on the training day.
Ya

Tidak
V. Delivery and installation at site of server as per instruction of UiTM without incurring any additional costs to UiTM.
Ya

Tidak