1. General Requirements
|
-
|
|
|
I. Vendors Is Allowed To Propose Specification Which Is Superior Than The Requirements Specified In This Document at UiTM as below :
Kampus Sungai Buloh : 31 Units
Kampus Teluk Intan : 2 Units
|
Ya Tidak
|
|
|
II. The proposed equipment must have a local services center to provide a full technical support and maintenance
|
Ya Tidak
|
|
|
III. All related catalogues/brochures shall be provided by the vendor
|
Ya Tidak
|
|
|
IV. **PLEASE DO NOT DISCLOSE ANY INFORMATION RELATED TO THE COMPANY'S NAME, LOGO, REGISTRATION NUMBER, ETC. THIS INFORMATION MUST BE ERASED AND NOT BE READABLE
Noted : Please reser tu UiTM staff for detailed installation location
|
Ya Tidak
|
|
|
2. TECHNICAL SPECIFICATION
|
Ya Tidak
|
|
|
I. The proposed equipment must provide comprehensive protection against surges and spikes
|
Ya Tidak
|
|
|
II. Must provide clean and stable power to connected equipment while its embedded microprocessor controller guarantees high reliability
|
Ya Tidak
|
|
|
III. Must provide Green Power Function to achieve lower power consumption for energy saving
|
Ya Tidak
|
|
|
IV. ELECTRICAL OUTPUT
|
Ya Tidak
|
|
|
A ) Voltage : 200/208/220/230/240VAC
|
Ya Tidak
|
|
|
B ) Frequency: 47- 53Hz or 57- 63Hz
|
Ya Tidak
|
|
|
C ) Phase : Single Phase
|
Ya Tidak
|
|
|
D ) Efficiency: 83% - 88% depending on load
|
Ya Tidak
|
|
|
E ) Voltage Distortion :less than 6% of THD at rate non-linear load : less than 3% of THD at rate linear load
|
Ya Tidak
|
|
|
V. POWER
|
-
|
|
|
A ) Rating: at least 2KVA at pf 0.9
|
Ya Tidak
|
|
|
B ) Rating: Double-Conversion Online UPS.
|
Ya Tidak
|
|
|
VI. ELECTRICAL INPUT
|
-
|
|
|
A ) Nominal Voltage : 200/208/220/230/240VAC
|
Ya Tidak
|
|
|
B ) Voltage Range: 110-300VAC at 50% Load, 160-280VAC at 100% Load
|
Ya Tidak
|
|
|
C ) Rated Frequency : 40Hz – 70Hz
|
Ya Tidak
|
|
|
D ) Power Factor: greater than 99% at Nominal Voltage (100% Load)
|
Ya Tidak
|
|
|
E ) Efficiency = 88% at AC Mode, 83% at Battery Mode.
|
Ya Tidak
|
|
|
VII. BATTERY
|
-
|
|
|
A ) Type: Sealed, Maintenance-free lead-acid battery
|
Ya Tidak
|
|
|
B ) Number of batteries: 9 Ah, 12 V, 4 pcs.
|
Ya Tidak
|
|
|
C ) Back-up time: 3 minutes at full load
|
Ya Tidak
|
|
|
D ) Recharge time: 4 hrs to 90% capacity
|
Ya Tidak
|
|
|
VIII. CONTROL FEATURES
|
-
|
|
|
A ) User Interface: Monitoring panel with LCD/LED display : UPS on, Line on, Battery operation, Bypass, Audible alarm
|
Ya Tidak
|
|
|
B ) Serial Communications Port: RS232
|
Ya Tidak
|
|
|
IX. ENVIRONMENTAL
|
Ya Tidak
|
|
|
A )
- Ambient Temperature:
- 0 degree celsius to 40 degree celsius operating
|
Ya Tidak
|
|
|
B ) Humidity: 20 to 90% RH non-condensing
|
Ya Tidak
|
|
|
C ) Audible Noise: 50 dBA (1M from surface)
|
Ya Tidak
|
|
|
X. PHYSICAL
|
Ya Tidak
|
|
|
A ) Dimension : 410mm x 438mm x 88mm (2u)
|
Ya Tidak
|
|
|
B ) At least weight : 19kg
|
Ya Tidak
|
|
|
C ) Type : 2-in-1 Rackmount-Tower (Display can be rotate)
|
Ya Tidak
|
|
|
XI. COMMUNICATIONS
|
-
|
|
|
A ) SNMP Web-Pro for Manage and Monitor UPS.
|
Ya Tidak
|
|
|
3. TECHNICAL/OPERATING MANUAL, ENGINEERING SERVICES & OTHER ACCESSORIES
|
-
|
|
|
I. User manual/operating manual must be provided by the vendor
|
Ya Tidak
|
|
|
II. All other related material, components and cabling which are not specified but required to ensure full operation must be supplied by the vendor
|
Ya Tidak
|
|
|
4. SUPPORT & WARRANTY
|
-
|
|
|
I. Delivery cost of the equipment is borne by the vendor
|
Ya Tidak
|
|
|
II. Must provide comprehensive and extensive after sales service on labor and overall parts
|
Ya Tidak
|
|
|
III. All other related software, material, components and cabling which are not specified but are required to
ensure full integration of the item MUST be provided.
|
Ya Tidak
|
|
|
5. INSTALLATION & TRAINING:
|
-
|
|
|
I. Pre requisite of requirement of installation, testing and commissioning on site for the supplied package and components MUST be done by tenderer
|
Ya Tidak
|
|
|
II. Tendered MUST provide Transfer Technology Session (TOT) training for configuration, operation and maintenance of the system which must cover Rack Mountable Base Unit System Intelligent and UPS Management Software for UiTM's personnel.(Plase specify details of the training by providing
syllabus/guideline).
|
Ya Tidak
|
|
|
III. Minimum of three (3) participants on Server and System Management training session
|
Ya Tidak
|
|
|
IV. Original training materials (hard copy and soft copy) and documentation MUST be provided on the training day.
|
Ya Tidak
|
|
|
V. Delivery and installation at site of server as per instruction of UiTM without incurring any additional
costs to UiTM.
|
Ya Tidak
|
|